We are using different testing method based on the battery type and usage. The battery tester is most common device to check the battery status immediately. A battery tester is an electronic device intended for testing the state of an electric battery, going from a simple device for testing the charge actually present in the cells and/or its voltage output, to a more comprehensive testing of the battery’s condition, namely its capacity for accumulating charge and any possible flaws affecting the battery’s performance and security.

There are some main reasons to test battery systems:

▪ To insure the supported equipment is adequately backedup
▪ To prevent unexpected failures by tracking the battery’s health
▪ What is the capacity and the condition of the battery now?
▪ When will it need to be replaced?
▪ What can be done to improve / not reduce its life?

Impedance Testing 

This is a non-intrusive test designed to build up a performance history of each battery cell. It is typically undertaken annually as this enables performance to be tracked over time. This makes it easier to identify any signs of deterioration or any cells with high internal impedance that might require replacing. Impedance testing involves applying an AC current to each battery via probes attached to the block terminals. Impedance is measured and recorded in milli ohms.  It gives a general indication of the batteries’ status without placing them under too much stress or needing to take them offline.  

Electro-Chemical Testing 

Another non-invasive check that compares the data from batteries to algorithms for common battery conditions, such as sulphation and electrolyte dry-out.  Traditionally, these tests were carried out in laboratories to predict battery failure on satellites and space vehicles. Now tests can be conducted using portable hand-held units.  This process uses probes on the terminals to measure the frequency response to voltage and current signals passed into the battery. These results are cross-referenced to performance data for “healthy” batteries. Because electro-chemical testing measures sulphation and electrolyte dry-out rather than just impedance, it is said to provide a more detailed summary of battery condition. Failing blocks can either be recharged at a higher rate to reduce sulphation or replaced completely. 

Load Bank Testing (Discharge Testing) 

This is the most comprehensive battery test and the only true examination that determines the actual capacity of the battery string. Load bank testing audits the batteries under both normal and peak load conditions. This demonstrates which cells hold the charge and highlights which might be approaching their end of service life. The Institute of Electrical and Electronics Engineers (IEEE) recommends performing discharge testing at the time of installation, then repeating the test every year. The main drawback of load bank testing is that the UPS batteries must be taken out of service during the test. Usually the batteries are available again within 24 hours, although in the worst-case scenario this can last for several days. 

Partial Discharge Testing

As the name suggests, this offers something of a middle ground. Partial discharge testing involves discharging the batteries up to a maximum of 80%. While this takes them out of action similar to load bank testing, they should be available again inside 8 hours.  If there’s a fault condition that requires the UPS to run off its batteries it can do so, although they will only have 20% of their full capacity.  

UPS Battery Monitoring 

In addition to battery testing, dedicated battery monitoring systems also measure UPS battery performance. It is advised all monitoring systems incorporate the parameters outlined by the globally-recognised IEEE 1491 standard, including: 

  • String and cell float voltage 
  • String and cell change and discharge voltage 
  • AC ripple voltage 
  • AC ripple current 
  • String charge current 
  • String discharge current 
  • Ambient and cell temperature 
  • Cell internal resistance 
  • Cycles. 